Hover to zoom · click for full screen

Rubber Matting CO Rubber Flooring › Rolls

High Voltage Electrical Safety Matting IEC 61111 Class 1 to 4, up to 36kV

★Excellent on Trustpilot SKU Rmco-3908
£101.95per metre inc. VAT
Thickness
3mm to 5mm
Use
Indoor
Width
Class 1 to 4, 1 m wide (Class 2 also 1.2 m), cut to length up to 10 m
Material
Rubber
Choose size
Key Features
  • IEC 61111:2009 Class 1, 2, 3 or 4
  • Rated from 7,500V up to 36,000V working
  • Class 2 for 11kV, Class 4 for 33kV switchgear
  • Proof and withstand tested to the standard

Description

Electrical Safety MattingSKU Rmco-3908

High voltage switchroom matting to IEC 61111:2009 in Class 1 to Class 4, for maximum working voltages from 7,500V up to 36,000V. Choose the class to suit your system: Class 2 is the usual choice for 11kV switchgear and Class 4 for 33kV. Every grade is proof and withstand tested to the standard, with mechanical puncture, slip, flame and low-temperature tests on top, and colour-coded class marking repeats along the underside every metre so any length can be identified at inspection.

Which class do I need?

Class Max working voltage Typical UK system Proof / withstand test Thickness and widths
Class 1 7,500 V 3.3kV and 6.6kV plant 10 kV / 20 kV 3 mm, 1 m wide
Class 2 17,000 V 11kV switchgear 20 kV / 30 kV 4 mm, 1 m or 1.2 m wide
Class 3 26,500 V 22kV systems 30 kV / 40 kV 4.5 mm, 1 m wide
Class 4 36,000 V 33kV substations 40 kV / 50 kV 5 mm, 1 m wide

Choose a class whose maximum working voltage is at or above the highest voltage in the work area. If you are not sure, call us before you order and we will help you pick the right grade.

Why choose this matting

Current standard

IEC 61111 replaced BS 921 and covers voltage, mechanical puncture, slip, flame and cold-weather performance, so it is the grade to specify for high voltage switchrooms and audits.

One page, every class

Class 1 to Class 4 side by side, so you can match the matting to 3.3kV, 6.6kV, 11kV, 22kV or 33kV equipment.

Marked every metre

Class marking runs along the underside at one-metre spacing in the IEC colour code: white for Class 1, yellow for Class 2, green for Class 3 and orange for Class 4.

Cut to length

Sold per linear metre from 1m up to a full 10m roll, so the full length in front of the switchgear can be covered in one piece.

Ideal for

  • 11kV switchrooms
  • 33kV substations
  • Ring main units
  • HV motor and plant rooms
  • Hospital and data centre intakes
  • Wind and solar farm substations
  • Rail and utility switchgear

Specifications

Standard IEC 61111:2009 (BS EN 61111), Class 1 to Class 4
Maximum working voltage 7,500 V (Class 1), 17,000 V (Class 2), 26,500 V (Class 3), 36,000 V (Class 4)
Thickness 3 mm, 4 mm, 4.5 mm or 5 mm, by class
Weight Approx. 4.5 to 7.5 kg per m², by class
Widths 1 m (Class 2 also 1.2 m)
Supplied Cut to length from 1 m to 10 m, or a full 10 m roll
Colour Black
Compound Insulating rubber, no recycled content
Top surface Fine lengthwise ribs
Underside Fabric-texture finish, colour-coded class marking every metre
Mechanical puncture 70 N minimum, at least 80% retained after 168 hours at 70°C
Slip resistance Average force above 50 N
Flame retardance Flame does not spread beyond 50 mm of the ignition point
Cold resistance No cracking or puncture after 4 hours at −25°C
Hardness 70–80 Shore A
Density 1.45–1.55 g/cm³
Tensile strength 4.9 MPa minimum
Elongation at break 200% minimum
Compliance REACH compliant
Sold as Price per linear metre

Fitting & care

  1. Lay the matting along the full working area in front of the switchgear, so the operator never stands off the mat.
  2. Use one continuous length where you can; avoid gaps or overlaps at joins.
  3. Keep the surface clean and dry, and wipe with mild soapy water. Do not use solvents or oils.
  4. Inspect before use for cuts, holes, embedded metal or damage, and replace any damaged section straight away.

FAQs

Which class do I need for 11kV?

Class 2, rated to 17,000V working, is the usual choice for 11kV switchgear. For 33kV choose Class 4. Always pick a class at or above the highest voltage in the work area, and call us if you are unsure.

What about low voltage panels?

For switchboards up to 1,000V, our Class 0 matting to IEC 61111 is the right grade and costs less.

Can I get a test certificate?

Call us before you order if you need a test certificate for your records and we will arrange it with your order.

How is the price worked out?

The price is per linear metre. Choose your class and width, then set the quantity to the number of metres you need, up to a full 10m roll.

Is matting enough on its own?

No. Insulating matting is one layer of protection. High voltage work must follow your safety rules, with authorised persons, isolation, permits and the right PPE.

Safety note: Insulating matting is an extra safeguard, not a replacement for isolating equipment, PPE and a safe system of work.
Not sure this is right for your job? Call 01204 961600 or WhatsApp us – we'll help you choose the right size and thickness.

Specifications

Product codeRmco-3908
SizeClass 1 (7.5kV) 1m Wide x 3mm Thick
CategoryRubber Flooring › Rolls
Sold asPer linear metre
Weight9.92 lb
BrandRubber Matting CO

Bulk & trade order

Need several sizes at once? Add them all from one list (quantities in metres). For one size, use the options at the top of the page.

Delivery & returns

Free UK mainland delivery

Dispatched from our UK warehouse within 24 hours. Shipping policy

14-day returns

Return unused items within 14 days. Returns policy

VAT invoice with every order

Switch prices between inc. and ex. VAT with the toggle by the price.